HT transmission line and tower earthing
HT transmission line Earthing
- The earth conductor is
placed on the top of structure tower to provide a shield angle over the power
conductor to protect against lightning stroke.
- The shield angle is usually
maintained at 25 degrees for outer and 45 degrees for the central conductor.
Specifications of
tower earthing
- Each 132KV transmission
tower leg to be provided with one single peg earth electrode.
- The electrode length shall
be 3 meters with 18 holes of 10mm at the bottom 1 m length.
- The electrode shall be 38 mm and 3.25 mm
thick.
- All the earthing pegs shall
be internally connected via 50*6mm GI flat.
- The connection of GI flat
to tower leg should be done at a height of min. 500mm from the ground level.